Modbus Action ​

The Modbus action writes register and coil values to Modbus TCP and Modbus RTU devices.

Properties ​

Property NameOptionalDescription
endpointfalseHost and port of the Modbus server (e.g. 192.168.1.50:502) or Unix device path.
modetrueProtocol framing mode: "tcp" (default) or "rtu_over_tcp" / "rtu".
unitIdtrueTarget slave unit ID (0..=255). Default: 1. Alias: slaveId.
functiontrueTarget function code: "holding" (FC06/FC16, default) or "coil" (FC05/FC15).
registerAddressfalse0-based wire address of the target register or coil.
fieldfalseThe field name in the output record whose value should be written.
dataTypetrueValue type: bool, uint16, int16, uint32, int32, uint64, int64, float32, float64. Default: uint16.
byteOrdertrueWord/byte layout for multi-register fields: ABCD (default), CDAB, BADC, or DCBA.
timeouttrueSocket write timeout (e.g. 1000ms). Default: 1000ms.

Other common sink properties are supported. Refer to sink common properties for more information.

Example ​

Write a setpoint to holding register 100:

json
{
  "id": "rule_chiller_actuation",
  "sql": "SELECT target_setpoint FROM telemetry_stream WHERE target_setpoint IS NOT NULL",
  "actions": [
    {
      "modbus": {
        "endpoint": "192.168.1.50:502",
        "unitId": 1,
        "function": "holding",
        "registerAddress": 100,
        "field": "target_setpoint",
        "dataType": "float32",
        "byteOrder": "CDAB"
      }
    }
  ]
}

Dead-Letter Queue (DLQ) Integration ​

When a write command fails with Modbus exception codes:

  • 0x01: Illegal Function
  • 0x02: Illegal Data Address
  • 0x03: Illegal Data Value

The engine classifies the failure as a permanent delivery error. It sends the output record to the dead-letter queue under DlqStage::SinkDelivery. For configuration options, refer to Dead-Letter Queues.